Electrical fault finding in York

Tripping RCDs, unexplained power loss, circuits that trip immediately on reset, burning smells, intermittent failures. Found properly with calibrated test equipment — not guesswork. Most faults diagnosed on the first visit.

✓ NICEIC Approved Contractor ✓ Calibrated Test Equipment ✓ £60+VAT per Hour ✓ Most Faults Found First Visit ✓ Clear Price Before Any Repair

What I can find and fix

RCD or RCBO tripping

Trips immediately on reset, trips randomly, or trips only when specific appliances are on. Diagnosed by circuit isolation and insulation resistance testing.

Total power loss

All circuits off and won’t reset. Could be the consumer unit, the meter tails, the supply fuse, or an active fault holding the RCD down. Diagnosed and made safe on the day.

Partial power loss

Some circuits working, others not. Could be a failed MCB, a tripped RCD section, a broken neutral, or a failed connection at the consumer unit. Most are straightforward once the fault is isolated.

Burning smell from socket or fitting

Treated as a priority. A burning smell from a socket indicates arcing at a loose connection, overloading, or insulation breakdown. Stop using the socket and call immediately. See the emergency page if urgent.

Intermittent faults

Faults that come and go are the most time-consuming to find but have a physical cause. Insulation resistance testing, connection checking, and environmental analysis. Most yield to methodical testing.

No power to a circuit or room

One room or circuit dead with no obvious trip at the board. Often a failed connection in a junction box or previous DIY work. Usually found within an hour.

How fault finding actually works

The difference between a proper fault diagnosis and guesswork is test equipment and methodology. A visual inspection tells you what you can see. A multifunction installation tester tells you the insulation resistance of every conductor in a circuit, the earth continuity, and the impedance at every point — and it finds faults that are completely invisible to the eye.

The process: identify which circuit is affected and confirm the symptoms. Isolate variables — appliances first, then fixed wiring. Test the circuit wiring with an insulation resistance meter to check for degraded insulation or earth leakage. Check continuity of the neutral conductor, which fails silently in ways that cause unpredictable behaviour. Inspect accessible connections at sockets, switches, and any junction boxes.

Most faults show up within the first hour of proper testing. When the cause is found, I’ll explain what it is and give you a clear price for the repair before doing anything. The fault finding charge is £60+VAT per hour. The repair is priced and agreed separately.

Before you call — what to try first

For an RCD that keeps tripping: unplug everything on the affected circuit and reset. If it stays on, plug things back one at a time — the one that trips it is the fault. If it trips with nothing plugged in, the fault is in the fixed wiring and I need to come out. See the full guide to tripping RCDs.

For a dead circuit: check the consumer unit for a tripped MCB or RCBO. Sometimes they trip to the middle position rather than fully off — push fully off and then back on. If it trips immediately on reset, call me. If the MCB isn’t tripped and the circuit is still dead, there’s likely a wiring fault or a failed connection.

Electrical fault finding in York

£60+VAT per hour. Tell me the symptoms and I’ll give you an honest view of what’s likely involved.

Call NowWhatsApp